Chapter 6 Control Mode of Operation
Note 1: When the value of P1-26 and P1-28 is 0, it means it is unable to search the frequency. It is
probably because the detection level is set too high and is unable to detect the low-frequency
vibration.
Note 2: When the value of P1-26 or P1-28 is not set to 0 and still cannot eliminate the vibration, it
is probably because the detection level is set too low, the system regards the noise or other non-
primary frequency as the low-frequency vibration.
Note 3: When the process of auto vibration suppression is completed and the vibration still cannot
be diminished, P1-25 or P1-27 can be manually set to suppress the vibration if the frequency (Hz)
of the low-frequency is identified.
Related parameters:
P1-29
AVSM
Operational
Interface:
Default: 0
Control
Mode:
Unit: -
Range: 0 ~ 1
Data Size: 16-bit
Format: Decimal
Settings: 0: The function is disabled.
P1-30
VCL
Operational
Interface:
Default: 500
Control
Mode:
6-20
Auto Low-frequency Vibration Supression
Setting
Panel / Software
PT / PR
1: The value will set back to 0 after vibration suppression.
Description of Auto Mode Setting:
When the parameter is set to 1, it is in auto suppression. When the
vibration frequency is not being detected or the value of searched
frequency is stable, the parameter will set to 0 and save the low-
frequency vibration suppression to P1-25 automatically.
Low-frequency Vibration Detection
Panel / Software
PT / PR
Communication
Communication
ASDA-A2
Address: 013AH
013BH
Related Section:
6.2.9
Address: 013CH
013DH
Related Section:
6.2.9