Chapter 7 Optional Accessories |CFP2000 Series

7-2 Non-fuse Circuit Breaker

Comply with UL standard: Per UL 508, paragraph 45.8.4, part a.
The rated current of the breaker shall be 1.6~2.6 times of the maximum rated input current of AC
motor drive.
VFD007FP4EA-41/ VFD007FP4EA-52/ VFD007FP4EA-52S
VFD015FP4EA-41/ VFD015FP4EA-52/ VFD015FP4EA-52S
VFD022FP4EA-41/ VFD022FP4EA-52/ VFD022FP4EA-52S
VFD040FP4EA-41/ VFD040FP4EA-52/ VFD040FP4EA-52S
VFD037FP4EA-41/ VFD037FP4EA-52/ VFD037FP4EA-52S
VFD055FP4EA-41/ VFD055FP4EA-52/ VFD055FP4EA-52S
VFD075FP4EA-41/ VFD075FP4EA-52/ VFD075FP4EA-52S
VFD110FP4EA-41/ VFD110FP4EA-52/ VFD110FP4EA-52S
VFD150FP4EA-41/ VFD150FP4EA-52/ VFD150FP4EA-52S
VFD185FP4EA-41/ VFD185FP4EA-52/ VFD185FP4EA-52S
VFD220FP4EA-41/ VFD220FP4EA-52/ VFD220FP4EA-52S
VFD300FP4EA-41/ VFD300FP4EA-52/ VFD300FP4EA-52S
VFD370FP4EA-41/ VFD370FP4EA-52/ VFD370FP4EA-52S
VFD450FP4EA-41/ VFD450FP4EA-52/ VFD450FP4EA-52S
VFD550FP4EA-41/ VFD550FP4EA-52/ VFD550FP4EA-52S
VFD750FP4EA-41/ VFD750FP4EA-52/ VFD750FP4EA-52S
VFD900FP4EA-41/ VFD900FP4EA-52/ VFD900FP4EA-52S
Model
7-4
Recommended non-fuse breaker (A)
6
6
10
15
15
20
25
35
50
60
60
90
100
125
150
200
250