2.9  Connecting Supply Power
SNMP/Notifications Hot Swap Monitoring
If your unit is configured with hot swappable power supplies, additional options
will be visible in the Web UI under MANAGEMENT > Notifications in the System
tab:
You can configure these notifications to be send via SNMP:
Notifications" on
Hot Swap Power Supply Alarms
There are two Hot Swap specific alarms:
The Hot Swap, Major Alarm will cause the status to appear red in the Web UI and
is triggered if one of the power supplies falls within the following thresholds:
The Hot Swap, Minor Alarm will cause the status to appear yellow in the Web UI
and is triggered if one of the power supplies falls within the following thresholds:
60
Note:
Disabling monitoring on a single bay will remove it from
consideration in the Overall Hot Swap Status and remove alarm-
ing for the bay.
page 269.
Voltage (< 11V) or (> 13V)
Current (> 9A)
Fan Speed (< 10,000 RPM) or (> 18,000 RPM)
Temperature AC sled (<-25 °C) or (> 85°C)
Temperature DC sled (<-40 °C) or (> 85°C)
Unknown Sled Type installed
CHAPTER
2
SecureSync 2400 User Manual Rev. 5.2