Table 5-2:
Troubleshooting using the Web UI Status indications
Web UI Page loc-
ation
HOME page, Sys-
tem Status panel,
Status row
SecureSync 2400 User Manual
Current Status
SYNC indicator is not
SecureSync is
"lit" (not Green).HOLD
in Holdover
indicator is "lit"
mode—OR—
(Orange).—OR—
SecureSync is
FAULT indicator is
now out of
"lit" (Red). Below the
Time Sync
System Status panel
there is an Out of
Sync alarm statement
Indication
Troubleshooting
All available Input References
have been lost. The Reference
Status table on the HOME page
will show the current status of
all inputs (Green is valid and
Red is invalid or not present).
1. Make sure the Input Reference
Priority table still has the
desired reference inputs
Enabled, based on the desired
priority. See
Input Reference Priorities"
on page 205
2. Make sure the desired input
references are still connected to
the correct input port of
SecureSync.
3. Verify GNSS antenna install-
ation (if applicable). See
"Troubleshooting GNSS
Reception" on page 357