2.20  Configuring Outputs
The Edit window allows the configuration of the following settings:
178
Signature
Control: Is used to control when the IRIG modulation will be
present. This function allows the modulation to stop under certain
conditions; see also
"Signature Control" on
Format: Used to configure the desired IRIG output formatting. The avail-
able choices are:
IRIG A
IRIG B
IRIG G
IRIG E
NASA-36
Modulation: Changes the type of output signal modulation. The available
choices are:
IRIG DCLS—A TTL-modulated output.
IRIG AM-–An amplitude modulated output. The amplitude of the out-
put is determined by the value entered in the Amplitude field.
Frequency—The IRIG modulation frequency. This is determined by
the configuration of Format and Modulation Type. See also
rier Frequencies" on
Coded
Expression: Defines the data structure of the IRIG signal, where:
BCD = Binary Coded Decimal
TOY = Time of Year
CF = Control Field
page 183.