7.3.2 Troubleshooting the FlexPendant

Description
The FlexPendant communicates with the main computer. The FlexPendant is
physically connected to the panel board. The cable contains the +24 V supply, two
enabling device chains and emergency stop.
Procedure
The procedure below describes what to do if the FlexPendant does not work
correctly.
1
2
3
4
5
For more information on the FlexPendant, see Operating manual - OmniCore.
Product manual - OmniCore C90XT
3HAC073706-001 Revision: E
Action
Try resetting the FlexPendant using the reset
button located next to the USB port.
If the FlexPendant is not responding or does not
operate correctly, see
Problem starting or con-
necting the FlexPendant on page
Check the cable for connections and integrity.
Check the 24 V power supply.
Read the error event log message and follow any
instructions of references.
© Copyright 2020-2021 ABB. All rights reserved.
7 Troubleshooting
7.3.2 Troubleshooting the FlexPendant
Note
See Operating manual - Omni-
Core.
Note
375.
If protective gloves are used, these
must be compatible with touch-
screens when using the FlexPend-
ant.