7 Troubleshooting
7.2.5 Problem starting or connecting the FlexPendant
Continued
2
3
4
5
6
7
8
378
Action
Check that the FlexPendant cable is correctly
connected to the controller through the HMI signal
connector, X4.
Check the LED PC and LED HMI, they should be
green.
Check the FlexPendant cable for any damage.
Check that the connection from the robot signal
exchange proxy to the HMI signal connector is
ok, K2.X9, 13 - X4.
Check that the connection from the robot signal
exchange proxy to the main computer is ok:
K2.X8 - A2.X6
K2.X2 - A2.X1
K2.X12 - A2.K3.X6,7
K2.X3 - A2.K3.X1
If possible, test by connecting another FlexPend-
ant. This is to eliminate the FlexPendant and cable
as error sources; Test the FlexPendant with a
different controller to eliminate the controller as
error source.
Check that the FlexPendant works normally.
Tip
This is detailed in section
FlexPendant on page
385.
© Copyright 2020-2021 ABB. All rights reserved.
Note
If it is not connected, repair the
connection and go to step six.
Check the pins in the connector.
If it is ok, go to the next step.
For more details about the LEDs,
see
nal exchange proxy on page
If it is not ok, contact your local
ABB.
Troubleshooting the
Product manual - OmniCore C90XT
Troubleshooting the robot sig-
If the LEDs are not green,
see
Troubleshooting the ro-
bot signal exchange proxy
on page
414.
If they are ok, go to the next
step.
If damage is found, replace
the FlexPendant cable and
go to step six.
If it is ok, go to the next
step.
If it is not ok, repair the con-
nection and go to step six.
If it is ok, go to the next
step.
If any connection fails, re-
pair the connection and go
to step six.
If the connections are ok, go
to the next step.
3HAC073706-001 Revision: E