5 Repair
5.2.8 Replacing the main computer
Continued
i
Concluding procedure
1
2
3
Continues on next page
246
Action
For the connected services gateway:
i
K7.X1 - K2.X3
K7.X2 - A2.X5
Note
The connector K7.X2 is locked;
grab the connector, push it in to
release it and then remove the
connector.
For the main computer:
A2.X3 - X24
K2.X8 - A2.X6
K2.X2 - K4.X8, A2.X1
K2.X12 - A2.K3.X6, A2.K3.X7
K6.X2 - A2.X9
A2.X5 - K7.X2
A2.X4 - K4.X6/K5.1.X5
Note
If the Ethernet extension switch is
installed, connect and disconnect
the connector A2.X4 to/from
K4.X6.
If the Ethernet extension switch is
not installed, connect and discon-
nect the connector A2.X4 to/from
K5.1.X5.
For Connected Services Gateway wired, there is no power cable.
Action
Close the door.
Restore the hardware settings.
Perform the function tests to verify that
the safety features work properly, see
Function tests on page
171.
© Copyright 2020-2021 ABB. All rights reserved.
Note/Illustration
Note/Illustration
Closing the door on page
Restoring the hardware settings on page
Product manual - OmniCore C90XT
3HAC073706-001 Revision: E
180.
247.