Concluding procedure
1
2
Product manual - OmniCore C90XT
3HAC073706-001 Revision: E
Action
Reconnect:
•
K2.X8 - A2.X6
•
(option): K2.X2 - K4.X8, A2.X1
•
K2.X12 - A2.K3.X6, A2.K3.X7
•
K2.X10 - A1.X13
•
K2.X21 - TempSensor (G3.TEMP)
•
K2.X4 - A1.X9
•
K2.X3 - K6.X1, A2.K3.X1, K5.1.X4,
K7.X1
•
K2.X1 - T2.X2
•
K2.X17 - G3.X1, G1.X2
•
K2.X6, K2.X11 - A1.X2
•
K2.X7, K2.X22 - Harn. LV robot
power (X1)
•
K2.X9 & X13 - FlexPendant (X4)
Action
Close the door.
Perform the function tests to verify that
the safety features work properly, see
Function tests on page
171.