4.5.5 Function test of auto stop

Performing the function test
1
2
Product manual - OmniCore C90XT
3HAC073706-001 Revision: E
Action
Start the robot system and change the op-
erating mode to auto mode.
Activate the auto stop, for example by
opening the connected robot cell door,
which has interlock connection with auto
stop.
© Copyright 2020-2021 ABB. All rights reserved.
4 Maintenance
4.5.5 Function test of auto stop
Note
The test is passed if the event message
20205 Auto stop open appears in the event
log.
If the event message 20205 Auto stop
open does not appear or if the event mes-
sage 20225 Auto stop conflict appears in
the event log, then the test has failed and
the root cause of the failure must be found.