7 Troubleshooting

7.2.3 System update failure

7.2.3 System update failure
Description
In certain scenarios, such as removing or adding certain optional features or major
upgrades of installed software products versions, the previous backup may be
incompatible with the newly re-configured system. Automatically reloading backup
can therefore fail, resulting in system failure state.
For more information about system update, see Operating manual - Integrator's
guide OmniCore.
Recommended working procedure
If there is a system update failure, the RobotWare system must be reset, which
will bring the system state to the default empty state for the current configuration.
See Operating manual - Integrator's guide OmniCore for detailed information
regarding system reset.
After reset, it is possible to:
See Operating manual - Integrator's guide OmniCore.
370
A Go forward with the new configuration by re-implementing your programs
and configuration, or selectively reloading contents of the previous system
backup
B Rollback the changes in the system configuration, that is, make a new system
update and load the previous backup, and then manually update as needed
C Perform a complete re-installation of the RobotWare System using RobotWare
Installation Utilities and then reloading the previous backup.