3.5.11 Programmable stop functions

Stopping functions
There are different methods to stop the robot, in addition to manually initiated
stops.
Stop category configuration
The stop category can be configured, see Technical reference manual - System
parameters.
Safety inputs
Automatic Stop
Emergency Stop
Emergency Stop
Stop with system input signals
In the control system, it is possible to define system input signals to be set/reset
through different interactions, for example, through networks, I/O blocks, RobAPI,
etc. See next release version.
Pre-defined system input
SoftStop
QuickStop
Stop at End of Cycle
Stop at End of Instruction
All of these stops are performed without using the brakes, and the power is never
disconnected. The program execution can be continued directly, for example by
activating a start signal.
Product manual - OmniCore C90XT
3HAC073706-001 Revision: E
Stop with system input signals
Stop with RAPID instructions
Other stops
System paramet-
er Function
Category1AS
Category1LES
Category1EES
Note
Only safety rated input signals are allowed to be used for safety.
© Copyright 2020-2021 ABB. All rights reserved.
3 Installation and commissioning
3.5.11 Programmable stop functions
Description
Category1AS can be used to configure the protective
stop in automatic mode either as stop category 0 or
category 1. The default configuration is TRUE (stop
category 1).
Category1LES is used to configure the emergency
stop on the FlexPendant in automatic and manual
mode. The default configuration is FALSE (stop cat-
egory 0).
Category1EES is used to configure an external emer-
gency stop in automatic and manual mode. The default
configuration is FALSE (stop category 0).
Description
The manipulator is stopped on the path with no deviation.
This is a faster stop of the manipulator than SoftStop. This stop
is more stressing for the mechanics than SoftStop. QuickStop
ignores torque and acceleration limits.
Stops the RAPID program when the complete program is ex-
ecuted, that means when the last instruction in the main routine
has been completed.
Stops program execution after the current instruction is com-
pleted.
Continues on next page