ABB Robotics OmniCore C90XT Product Manual page 405

Table of Contents

Advertisement

B
C
Description
Power status, PC
PWR (green)
Disk status, PC
HDD
Computer status,
PC STAT
(red/green)
For information about the LEDs on the AnybusCC slave fieldbus adapter and the
PCIExpress master/slave fieldbus board, see the corresponding fieldbus manual.
Product manual - OmniCore C90XT
3HAC073706-001 Revision: E
HDD status LED
Status LED
Significance
The power status LED indicates the status of the power supply and the
main computer hardware and firmware.
Normal behavior:
Off: During a normal startup the LED is off, until the COM Express
module inside the computer unit is started.
On solid: After completion of startup the LED is steady on.
Failure during startup (off between blinks). One to four short blinks, one
second off. This is repeated until power off.
Internal fail of power, FPGA, and/or the COM Express module.
Replace the computer unit.
Power failure during runtime (fast flashing between blinks). One to five
blinks, 20 fast flashing blinks. This is repeated until power off.
Temporary voltage drop, cycle the power to the controller.
Check the power supply voltage to the computer unit.
Replace the computer unit.
The disk status LED indicates access to the main computer persistent
memory.
Normal behavior:
No color at power on: R34 FPGA is loaded on the main board.
Yellow: Access (read/write) to internal mass memory.
The computer status LED indicates the startup progress of RobotWare
on the main computer.
Normal behavior:
1 Red, solid: Default when turning on the power.
2 Red, flashing: Initial self-test is ongoing and the operating system
is loading.
3 Green, even flashing (~1Hz): The operating system is loaded and
RobotWare is initializing.
4 Green, uneven flashing: The RobotWare system failed to load or
is not installed.
5 Green, solid: The computer is operational and the RobotWare
system is fully loaded.
If the LED does not turn steady green after approximately 5 minutes then
the LED can be used to identify the following issues:
No color: The internal power initialization failed. Restart the con-
troller. Replace the main computer if the problem remains.
Red, solid: Internal error. Restart the controller. Replace the main
computer if the problem remains.
Red, flashing continuously: Failed to load the operating system.
Restart the controller. See
Replace the main computer if the problem remains.
Green, even flashing continuously (~1Hz): Failure during start up.
Check error messages on FlexPendant. See
start on page
Green, uneven flashing: RobotWare Installation Utilities mode.
© Copyright 2020-2021 ABB. All rights reserved.
7 Troubleshooting
7.3.9 Troubleshooting the main computer
Controller fails to start on page
380.
Continues on next page
Continued
380.
Controller fails to
405