18.4.2 Connecting to SIMATIC S7-200
1
Communication settings
Set the communication settings of PLC and PC/PPI cable.
(1) PLC settings
Set the communication settings of PLC by operating the SIEMENS programing tool(STEP7-
WIN32).
Transmission speed*1
Data bit
Parity bit
Stop bit
*2
Host address
*1 Adjust with GOT settings.
*2 Set the address without overlapping the address of other units.
(2) PC/PPI cable settings
Set the transmission speed by operating the DIP switch on the PC/PPI cable.
DIP switch(down side:0, upper side:1)
1
0
1
0
1 2 3 4 5
SWITCH1
SWITCH2
0
0
0
0
*1 Adjust with GOT settings.
Setting item
RS-232
PC/PPI cable
SWITCH 123
SWITCH 4
SWITCH 5
SWITCH3
SWITCH4
SWITCH5
0
0
0
0
0
0
PLC settings
9600bps,19200bps
8-bit(fixed)
Even(fixed)
1-bit(ifixed)
1 to 31
RS-485
Transmission speed
*1
19200bps
*1
9600bps

18.4 PLC Side Setting

18.4.2 Connecting to SIMATIC S7-200
S7-200 CPU
18 - 21
17
18
19
20
21
22