Rs-232 Cable - Mitsubishi GOT1000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT1000 Series:
Table of Contents

Advertisement

21.2.1 RS-232 cable

The following shows the connection diagrams and connector specifications of the RS-232 cable used for
connecting the GOT to a temperature controller.
1
Connection diagram
(1) RS-232 cable 1)
GOT side
Signal name
Pin No.
1
RD(RXD)
2
SD(TXD)
3
ER(DTR)
4
SG
5
DR(DSR)
6
RS(RTS)
7
CS(CTS)
8
NC
9
FG
*1 For details on the setting method of the TERMINAL mode, refer to the following.
Cable connection and signal direction
Section 21.4.5 Connecting CMC10L
YAMATAKE product side
Interface converter(CMC10L)
TERMINAL
Mode *1
Signal name
Pin No.
3
SD
2
RD
5
SG
9
CS
8
RS
21.2 Connection Cable
21.2.1 RS-232 cable
17
18
19
20
21
22
23
24
21 - 15

Hide quick links: