Mitsubishi GOT1000 Series Connection Manual page 592

Graphic operation terminal
Hide thumbs Also See for GOT1000 Series:
Table of Contents

Advertisement

2
Communication detail settings
Item
Transmission Speed
Startup Time
Host Address
Delay Time
15 - 22
15.3 Preparatory Procedure for Monitoring
15.3.3 Setting communication interface (Communication settings)
Description
Set this item when change the transmission speed used for com-
munication with the connected equipment.
<Default: 19200bps>
Specify the time period from the GOT startup until GOT starts the
communication with the PLC CPU.
<Default: 3 seconds>
Specify the host address (station No. of the PLC to which the GOT
is connected) in the network of the GOT.
<Default: 1>
Set this item to adjust the transmission timing of the communica-
tion request from the GOT.
<Default: 0 ms>
Range
4800bps, 9600bps, 19200bps,
38400bps, 57600bps
3 to 30 seconds
1 to 31
0 to 30 (
10 ms)