Mitsubishi GOT1000 Series Connection Manual page 419

Graphic operation terminal
Hide thumbs Also See for GOT1000 Series:
Table of Contents

Advertisement

2
Communication detail settings
Item
Transmission Speed
Data Bit
Stop Bit
Parity
Retry
Timeout Time
Host Address
Delay Time
Station No. Selection
Description
Set this item when change the transmission speed used for
communication with the connected equipment.
<Default: 9600bps>
Set this item when change the data length used for
communication with the connected equipment.
<Default: 8bit>
Specify the stop bit length for communications.
<Default: 1bit>
Specify whether or not to perform a parity check, and how it is
performed during communication.
<Default: Even>
Set the number of retries to be performed when a
communication error occurs.
When receiving no response after retries, the communication
times out.
<Default: 0 Times>
Set the time period for a communication to time out.
<Default: 3 Sec>
Specify the host address (station No. of the PLC to which the
GOT is connected) in the network of the GOT.
<Default: 0>
Set this item to adjust the transmission timing of the
communication request from the GOT.
<Default: 0>
Specify whether to use the station No. during communication.
If [Yes] is selected, the station No. is fixed to "0."
<Default: No>
10.3 Preparatory Procedures for Monitoring
10.3.3 Setting communication interface (Communication settings)
Range
9600bps, 19200bps, 38400bps,
57600bps, 115200bps
7bit/8bit
1bit/2bit
None
Even
Odd
0 to 5 Times
3 to 30 Sec
0 to 9
0 to 300 ms
Yes or No