Mitsubishi GOT1000 Series Connection Manual page 190

Graphic operation terminal
Hide thumbs Also See for GOT1000 Series:
Table of Contents

Advertisement

(e) A2CCPUC24, A2CCPUC24-PRF
Transmission specifications
• Transmission speed setting (SW11 to SW13)
Set the transmission speed (SW11 to SW13) as follows.
The transmission speed setting must be consistent with that of the GOT side.
For how to set the GOT side transmission speed, refer to the following.
*1
Only transmission speeds available on the GOT side are shown.
(3) Station number setting switch
Station number setting switch
*2
The station number setting switch in the figure is for the A1SJ71UC24-R4.
4 - 50
4.4 PLC Side Setting
4.4.3 Connecting computer link module
Setting
switch
switch
SW11
SW12
SW13
ON
OFF
SW14
SW
11
SW15
12
13
SW16
14
15
16
SW17
17
SW18
18
19
SW19
20
SW20
Section 4.3.3 Setting communication interface (Communication settings)
Setting switch
SW11
SW12
SW13
*2
STATION NO.
10
1
When the switch setting has been changed
Turn the PLC CPU OFF then ON again, or reset the PLC CPU.
Description
(Consistent with the
Transmission speed
GOT side
setting
specifications.)
Data bit setting
8 bits
Parity bit setting
Set
Even/odd parity
Odd
setting
Stop bit setting
1 bit
Sum check setting
Set
Main channel setting
RS-232
Write during RUN
enabled/disabled
Enabled
setting
Transmission speed
4800bps
9600bps
OFF
OFF
ON
Description
Set the station number of the computer link module
to which an access is made from the GOT.
Setting
See descriptions
below.
*1
19200bps
ON
OFF
OFF
ON
ON
ON
Setting
ON
ON
OFF
OFF
ON
OFF
ON
0