Mitsubishi GOT1000 Series Connection Manual page 664

Graphic operation terminal
Hide thumbs Also See for GOT1000 Series:
Table of Contents

Advertisement

2
Connecting to DH485 network via adapter (1770-KF3) (Setting of Adapter)
*1
Baud Rate
Parity
Flow Control
DF1 Device Category
*2
Error Detection
DH-485 Baud Rate
Maximum Node Address
DH-485 Node Address
*1
*2
Set the Error Detection according to the sum check format setting on the GOT side.
*3
For the Maximum Node Address, set the same address as the Maximum Node Address on the DH-485 network.
*4
Set the DH-485 Node Address according to the Host Address on the GOT side.
17 - 24
17.4 PLC Side Setting
17.3.7 Checking for normal monitoring
Item
Set the Baud Rate according to the transmission speed setting on the GOT side.
For the transmission speed setting on the GOT side, refer to the following.
Section 17.3.3 Setting communication interface (Communication settings)
For the sum check format setting on the GOT side, refer to the following.
Section 17.3.3 Setting communication interface (Communication settings)
Set a unique DH-485 Node Address so that it does not conflict with the Node Address of the PLC CPU on the
DH-485 network.
For the Host Address setting on the GOT side, refer to the following.
Section 17.3.3 Setting communication interface (Communication settings)
Setting details
4800bps, 9600bps, 19200bps
Even
Disable (No Handshaking)
DF1 half-duplex slave, local mode
BCC
19200bps
*3
1 to 31
*4
0 to 31