21.4.2 Connecting SDC40A/40B/40G

1
Communication settings
Make the communication settings by operating the key of the temperature controller.
Setting items
*1
Transmission speed
Data length
*1
Parity bit
Stop bit
*2*3
Station address
*1
Set the transmission speed according to the baud rate of the GOT side.
*2
Do not set to "0".
*3
Select the station address without overlapping with that of other unit.
21.4.3 Connecting SDC15, SDC25/26, SDC35/36
1
Communication settings
Make the communication settings by operating the key or Smart Loader Package (SLP-C35) of the
temperature controller.
Setting items
*1
Transmission speed
*2
Communication mode
*1
Data length
*1
Parity bit
*1
Stop bit
Communication minimum response time
*3*4
Station address
*1
Set the transmission speed according to the baud rate of the GOT side.
*2
Set to CPL.
*3
Do not set to "0".
*4
Select the station address without overlapping with that of other units.
9600bps
8 bits
Even, none
1bits, 2bits
0 to 127
9600bps, 19200bps
CPL
7bits, 8bits
Odd, even, none
1bits, 2bits
1 to 250ms
0 to 127
21.4 Temperature Controller Side Setting
21.4.2 Connecting SDC40A/40B/40G
Set value
Set value
17
18
19
20
21
22
23
24
21 - 39