Mitsubishi GOT1000 Series Connection Manual page 266

Graphic operation terminal
Hide thumbs Also See for GOT1000 Series:
Table of Contents

Advertisement

(2) Setting from sequence program
The parameter is written to the buffer memory, and the data link is automatically started when PLC
CPU status changes from STOP to RUN.
(a) CC-Link module I/O signal
(b) Device used by user
(c) Buffer memory settings used in the present example
Buffer memory address
Decimal (Hexadecimal)
*1
Details for the station data are shown below.
For 1) and 2), set according to the station number setting switch of the CC-Link communication unit and condition
setting switches (SW2).
For 3), the setting is fixed.
1) Station No. (set it according to the station number setting switch.)
2) Number of stations occupied (set it according to the condition setting switches (SW2).)
3) Station type (2
6 - 30
6.3 PLC Side Setting
6.3.2 Connecting to CC-Link module (QnA Series)
Control & Communication Link System Master/Local Module Type AJ61QBT11/
A1SJ61QBT11 User's Manual
Device
M100, M101
Flag for parameter setting
M102, M103
Flag for data link startup
D0
Number of connected modules
D1
Number of retry
D2
No. of automatic return stations
D3
Operation specification in the case of CPU failure
D4
Reserved station specification (Station No. 1 to Station No. 16)
D5
Error invalid station specification (Station No. 1 to Station No. 16)
D6
Station data (first module)
D400
Error code in the case of data link startup failure
1 (1
)
Number of connected modules
H
2 (2
)
Number of retry
H
3 (3
)
Number of automatic return stations
H
6 (6
)
Operation specification in the case of CPU failure
H
16 (10
)
Reserved station specification (Station No. 1 to Station No. 16)
H
20 (14
)
Error invalid station specification (Station No. 1 to Station No. 16)
H
32 (20
)
Station data (first module)
H
b15
to
b12
b11
to
3)
2)
01
to 40
: Station No. 1 to Station No. 64
H
H
1
: Exclusive station 1
H
2
: Exclusive station 2
H
3
: Exclusive station 3
H
4
: Exclusive station 4
H
: Set it to intelligent device station.)
H
0
: Remote I/O station
H
1
: Remote device station
H
2
: Intelligent device station (Incl. local station)
H
Application
Item
*1
b8
b7
to
1)
Setting
1 (1 module)
3 (3 times)
1 (1 station)
0 (stop)
0 (No specification)
0 (No specification)
2101
H
b0