30.2 Connection Cable
The RS-422 cables for connecting multiple GT11s must be prepared by the user.
The following provides connection diagrams for each cable, connector specifications and other information.
1
Connection diagram
GOT side
Signal name
Pin No.
SDA
1
RDA
2
RSA
3
CSA
4
SG
5
SDB
6
RDB
7
RSB
8
CSB
9
2
Connector specifications
(1) GOT side connector
Use the following as the RS-422 interface connector on the GOT.
For the GOT side of the RS-422 cable, use a connector and connector cover applicable to the GOT
connector.
(a) Connector type
9-pin D-sub (female)
(b) Connector model
GT11
3
Precautions when preparing a cable
The length of the RS-422 cable must be 30m or less.
30 - 4
30.2 Connection Cable
Cable connection and signal direction
GOT
17LE-13090-27(D3AC)
Model
GOT side
Signal name
1
2
3
4
5
6
7
8
9
Manufacturer
DDK Ltd.
Pin No.
SDA
RDA
RSA
CSA
SG
SDB
RDB
RSB
CSB