16.2.1 RS-232 cable
The following shows the connection diagrams and connector specifications of the RS-232 cable used for
connecting the GOT to a PLC.
1
Connection diagram
(1) RS-232 cable 1)
GOT side
Signal name
Pin No.
*1
CD/NC
1
RD(RXD)
2
SD(TXD)
3
ER(DTR)
4
SG
5
DR(DSR)
6
RS(RTS)
7
CS(CTS)
8
9
*1
GT15:CD, GT11:NC
(2) RS-232 cable 2)
GOT side
Signal name
Pin No.
*2
CD/NC
1
RD(RXD)
2
SD(TXD)
3
ER(DTR)
4
SG
5
DR(DSR)
6
RS(RTS)
7
CS(CTS)
8
9
*3
Shell
*2
*3
Connect the shield to the housing of the connectors on both the GOT and YOKOGAWA product sides.
16 - 8
16.2 Connection Cable
16.2.1 RS-232 cable
Cable connection and signal direction
Cable connection and signal direction
GT15: CD, GT11: NC
YOKOGAWA product side
Pin No.
Signal name
2
RD
3
SD
5
SG
SHIELD
YOKOGAWA product side
Pin No.
Signal name
1
2
RD
3
SD
4
ER
5
SG
6
DR
7
RS
8
CS
9
*3
Shell

Hide quick links: