16.4.3 Connecting PC link module (F3LC11-1F, F3LC12-1F)

1
Switch setting on the PC link module
Set the switches accordingly.
(1) Transmission speed switch (SW1)
Set the same transmission speed setting as that of the GOT side.
For the transmission speed setting on the GOT side, refer to the following.
(2) Data format switch (SW2)
Set the character length, parity, stop bit and checksum consistent with the corresponding settings
on the GOT side.
For the settings on the GOT side, refer to the following.
16 - 32
16.4 PLC Side Setting
16.4.3 Connecting PC link module (F3LC11-1F, F3LC12-1F)
Switch setting
Set the switches before mounting the PC link module to the base unit.
F3LC11-1F
A
Section 16.3.3 Setting communication interface (Communication settings)
*1 Only transmission speeds available on the GOT side are shown.
Section 16.3.3 Setting communication interface (Communication settings)
1
O
F
2
F
3
4
5
6
7
8
F3LC12-1F
1
Side view indicated by A
With right side cover
removed
2
SW3
O
F
F
A
*1
Setting
4
5
7
9
A
C
Switch No.
Description
1
Character length
2
Parity
3
4
Stop bit
5
Checksum
End character
6
specification
7
Protect function
8
Security function
SW1
(1)
SW2
1
O
1
2
F
2
F
3
3
(2)
4
4
5
5
6
6
7
7
8
8
(3)
Transmission speed
4800bps
9600bps
19200bps
38400bps
57600bps
115200bps
Setting
ON (8 bits), OFF (7 bits)
ON, OFF
ON (even), OFF (odd)
ON (2 bits), OFF (1 bit)
ON, OFF
OFF
OFF (disabled)
OFF (disabled)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents