Mitsubishi GOT1000 Series Connection Manual page 1165

Graphic operation terminal
Hide thumbs Also See for GOT1000 Series:
Table of Contents

Advertisement

5
When the FA transparent function is used in a bus connection
(1) When GOT monitoring is faulty
The FA transparent function cannot be used in case that the GOT monitoring is faulty due to PLC
CPU errors or faulty communication between the PLC CPU and GOT.
When GOT monitoring is faulty, check the following.
1
Whether the PLC CPU operates normally
Refer to the User's Manual of the PLC CPU you use.
2
Whether the PLC CPU and GOT are connected normally
• Chapter 2 BUS CONNECTION
• Chapter 3 DIRECT CONNECTION TO CPU
(2) When mutiple GOTs are bus-connected
When multiple GOTs are bus-connected, the FA transparent function can be used on each GOT.
However, note that the monitoring performance of each GOT slows down as the number of
monitoring GOTs and PCs increases.
(3) When the FA transparent function is used in a bus connection
When the FA transparent function is used in a bus connection, the following GX Developer
functions cannot be executed.
The message "The executed function is not supported. Please check the manual and other
documentation." is displayed on GX Developer
Unsupported GX Developer functions
• Remote Reset
• Remote system reset
• Remote RUN
• Remote STOP
• Remote PAUSE
• Remote STEP-RUN
• Remote latch clear
• Write clock data
• Clear malfunction log
RS-232
Cable
PC
Inexecutable only when specify all stations/groups has been
performed.
29.5.1 Precautions common to each software
Remarks
29 - 21
29.5 Precautions