Mitsubishi GOT1000 Series Connection Manual page 312

Graphic operation terminal
Hide thumbs Also See for GOT1000 Series:
Table of Contents

Advertisement

2
Communication detail settings
Item
GOT NET No.
GOT PC No.
GOT IP Address
GOT Port No.
(QJ71E71/AJ71(Q)E71)
GOT Port No.
(Ethernet Download)
Default Gateway
Subnet Mask
Retry
Startup Time
*1
Timeout Time
8 - 8
8.2 Preparatory Procedures for Monitoring
8.2.3 Setting communication interface (Communication settings)
Description
Set the network No. of the GOT.
<Default: 1>
Set the station No. of the GOT.
<Default: 1>
Set the IP address of the GOT.
<Default: 192.168.0.18>
Set the GOT port No. for the connection with the Ethernet module.
<Default: 5001>
Set the GOT port No. for Ethernet download.
<Default: 5014>
Set the router address of the default gateway where the GOT is
connected. (Only for communication via router)
<Default: 0.0.0.0>
Set the subnet mask for the sub network. (Only for connection via
router)
If the sub network is not used, the default value is set.
<Default: 255.255.255.0>
Set the number of retries to be performed when a communication
error occurs.
When receiving no response after retries, the communication
times out.
<Default: 3 Times>
Specify the time period from the GOT startup until GOT starts the
communication with the PLC CPU.
<Default: 3 Sec>
Set the time period for a communication to time out.
<Default: 3 Sec>
Range
1 to 239
1 to 64
0.0.0.0 to 255.255.255.255
1024 to 5010, 5014 to 65534
(Except for 5011, 5012 and 5013)
1024 to 5010, 5014 to 65534
(Except for 5011, 5012 and 5013)
0.0.0.0 to 255.255.255.255
0.0.0.0 to 255.255.255.255
0 to 5 Times
3 to 255 Sec
3 to 90 Sec
(Continued to next page)