Connecting To Melsecnet/H Network Module - Mitsubishi GOT1000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT1000 Series:
Table of Contents

Advertisement

5.3 PLC Side Setting
MELSECNET/H network module
MELSECNET/10 network module (QnA Series)
MELSECNET/10 network module (A Series)
5.3.1

Connecting to MELSECNET/H network module

This section describes the settings of the GOT and MELSECNET/H network module in the case of system
configuration shown as
To connect the MELSECNET/H network module to the MELSECNET/10 network system, specify the
MELSECNET/10 Mode as a network type.
1
System configuration
MELSECNET/10 (PLC to PLC network)
*1
The MELSECNET/H network module is mounted at slot 0 of the base unit.
The start I/O No. of the MELSECNET/H network module is set at "0".
5 - 24
5.3 PLC Side Setting
5.3.1 Connecting to MELSECNET/H network module
Model name
QJ71LP21, QJ71LP21-25,
QJ71LP21S-25, QJ71BR11
AJ71QLP21, AJ71QLP21S,
AJ71QBR11, A1SJ71QLP21,
A1SJ71QLP21S, A1SJ71QBR11
AJ71LP21, AJ71BR11, A1SJ71LP21,
A1SJ71BR11
.
MELSECNET/H network module
For details of the MELSECNET/H network module, refer to the following manual.
Q corresponding MELSECNET/H Network System Reference Manual
(PLC to PLC network)
<MELSECNET/H network module> *1 (Use the default value for settings other
Station No.
Mode
Network type
Network No.
Total stations
Network range assignment: LB0000
Switch setting of MELSECNET/H network module
[Network parameter] of GX Developer
[Communication settings] of GT Designer2
5
Setting of the MELSECNET/10 communication unit
<GOT> (Use the default value for settings other
than the following.)
than the following.)
: 1
: Online (10Mbps)
: MNET/10 mode (Control station)
: 1
: 2
to LB00FF
H
H
LW0000
to LW00FF
H
H
Reference
Section 5.3.1
Section 5.3.2
Section 5.3.3
LW0100
to LW01FF
H
H