3
[Network parameter] of GX Developer
(1) Network parameter
No. of boards in module
Start I/O No.
Operational setting
Type
Mode
All connect count
Remote input (RX)
Remote output (RY)
Remote register (RWr)
Remote register (RWw)
Special relay (SB)
Special register (SW)
Retry count
Automatic reconnection station count
Stand by master station No.
PLC down select
Scan mode setting
Delay information setting
Station information setting
Remote device station initial setting
Interrupt setting
6 - 22
6.3 PLC Side Setting
6.3.1 Connecting to CC-Link module (Q Series)
Item
Setting
1
0000
H
(Use default value.)
Master station (fixed)
Remote net (Ver.1 mode)
1
X400
Y400
D300
D200
SB0
SW0
(Use default value.)
Refer to (2).
(Use default value.)
: Necessary
Setting necessity at GOT
connection
: As necessary
: Not necessary