Connecting To Melsecnet/10 Network Module (A Series) - Mitsubishi GOT1000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT1000 Series:
Table of Contents

Advertisement

5.3.3

Connecting to MELSECNET/10 network module (A Series)

This section describes the settings of the GOT and MELSECNET/10 network module (A Series) in the case
of system configuration shown as
In this section, the network parameter (common parameter) of GX Developer is taken as an exmaple to
provide explanations.
1
System configuration
MELSECNET/10 (PLC to PLC network)
Switch setting of MELSECNET/10 network module
[Network parameter] of GX Developer
*1
The MELSECNET/10 network module is mounted at slot 0 of the base unit.
The start I/O No. of the MELSECNET/10 network module is set at "0".
5 - 36
5.3 PLC Side Setting
5.3.3 Connecting to MELSECNET/10 network module (A Series)
.
MELSECNET/10 network module (A Series)
For details of the MELSECNET/10 network module (A Series), refer to the following
manual.
Type MELSECNET/10 Network system (PLC to PLC network) Reference
Manual
<MELSECNET/10 network module> *1 (Use the default value for settings other
Station No.
: 1
Mode
: Online
Network type
: MNET/10 (Controlling station)
Network No.
: 1
Total stations
: 2
Network range assignment: LB0000
[Communication settings] of GT Designer2
Setting of the MELSECNET/10 communication unit
5
<GOT> (Use the default value for settings other
than the following.)
than the following.)
to LB00FF
H
H
LW0000
to LW00FF
H
H