Download Print this page

Siemens SINAMICS G120 List Manual page 1220

Cu250s-2 control units
Hide thumbs Also See for SINAMICS G120:

Advertisement

4 Faults and alarms
4.2 List of faults and alarms
34 (= 22 hex):
Timeout in the telegram receive list.
64 (= 40 hex):
Timeout in the telegram send list.
98 (= 62 hex):
Error at the transition to cyclic operation.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
- check the supply voltage of the component involved.
- carry out a POWER ON.
- replace the component involved.
F36886
Hub DRIVE-CLiQ (CU): Error when sending DRIVE-CLiQ data
Message class:
Internal (DRIVE-CLiQ) communication error (12)
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
DRIVE-CLiQ communication error from DRIVE-CLiQ Hub Module in question to Control Unit.
Data were not able to be sent.
Fault cause:
65 (= 41 hex):
Telegram type does not match send list.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
Carry out a POWER ON.
F36887
Hub DRIVE-CLiQ (CU): Component fault
Message class:
Internal (DRIVE-CLiQ) communication error (12)
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
Fault detected on the DRIVE-CLiQ component (DRIVE-CLiQ Hub Module) involved. Faulty hardware cannot be
excluded.
Fault cause:
32 (= 20 hex):
Error in the telegram header.
35 (= 23 hex):
Receive error: The telegram buffer memory contains an error.
66 (= 42 hex):
Send error: The telegram buffer memory contains an error.
67 (= 43 hex):
Send error: The telegram buffer memory contains an error.
96 (= 60 hex):
Response received too late during runtime measurement.
97 (= 61 hex):
Time taken to exchange characteristic data too long.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
- check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...).
- check the electrical cabinet design and cable routing for EMC compliance
- if required, use another DRIVE-CLiQ socket (p9904).
- replace the component involved.
1220
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890

Hide quick links:

Advertisement

loading