4 Faults and alarms
4.2 List of faults and alarms
Remedy:
Carry out the following steps on the TM54F:
- check the specified parameters for incorrect parameterization.
- activate the safety commissioning mode (p0010 = 95).
- start the copy function for SI parameters (p9700 = 57 hex).
- acknowledge complete data change (p9701 = AC hex).
- exit the safety commissioning mode (p0010 = 0).
- save all parameters (p0977 = 1).
- carry out safe acknowledgment (p10006).
For an internal software error (aaaa > 0):
- For TM54F, upgrade the firmware to a later version.
- contact Technical Support.
- replace the TM54F.
F35052 (A)
TM54F: Internal hardware error
Message value:
%1
Message class:
Hardware/software error (1)
Drive object:
B_INF, TM54F_MA, TM54F_SL, VECTOR_G
Component:
Terminal Module (TM)
Reaction:
NONE
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
An internal software/hardware error has been detected on the Terminal Module 54F (TM54F).
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- check the electrical cabinet design and cable routing for EMC compliance
- upgrade TM54F firmware to more recent version.
- contact Technical Support.
- replace the TM54F.
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F35053
TM54F: Temperature fault threshold exceeded
Message value:
%1
Message class:
Overtemperature of the electronic components (6)
Drive object:
B_INF, TM54F_MA, TM54F_SL, VECTOR_G
Component:
Terminal Module (TM)
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The temperature measured using the temperature sensing on the TM54F has exceeded the threshold value to
initiate this fault.
As fault response fail-safe input terminal signals are transferred to the motion monitoring functions.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- allow the TM54F to cool down.
- carry out safe acknowledgment (p10006).
A35054
TM54F: Temperature alarm threshold exceeded
Message value:
%1
Message class:
Overtemperature of the electronic components (6)
Drive object:
B_INF, TM54F_MA, TM54F_SL, VECTOR_G
Component:
Terminal Module (TM)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The temperature measured using the temperature sensing on the TM54F has exceeded the threshold value to
initiate this alarm.
Remedy:
- allow the TM54F to cool down.
- carry out safe acknowledgment (p10006).