4 Faults and alarms
4.2 List of faults and alarms
Remedy:
Check the wiring of the F-DIs and F-DOs and restart the test stop.
Note:
The fault is withdrawn if the test stop is successfully completed.
For fault value = CCCCCCCC hex, DDDDDDDD hex, EEEEEEEE hex the following applies:
These fault values occur together with fault F35152. Possible countermeasure:
- check all parameters for the test stop.
- you should also check whether the firmware version of the TM54F matches that of the Control Unit.
- check p10001, p10017, p10046 and p10047.
A POWER ON must be carried out after correcting the parameters.
F-DI: Failsafe Digital Input
F-DO: Failsafe Digital Output
A35014
TM54F: Test stop for fail-safe digital inputs/outputs
Message value:
-
Message class:
Safety monitoring channel has identified an error (10)
Drive object:
B_INF, TM54F_MA, TM54F_SL, VECTOR_G
Component:
Terminal Module (TM)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The time set in p10003 for the forced checking procedure (test stop) for the digital inputs/outputs has been exceeded.
A new forced checking procedure is required.
After the next time the forced checking procedure is selected, the message is withdrawn and the monitoring time is
reset.
Note:
- this message does not result in a safety stop response.
- the test must be performed within a defined, maximum time interval (p10003, maximum of 8760 hours) in order to
comply with the requirements as laid down in the standards for timely fault detection and the conditions to calculate
the failure rates of safety functions (PFH value). Operation beyond this maximum time period is permissible if it can
be ensured that the forced checking procedure is performed before persons enter the hazardous area and who are
depending on the safety functions correctly functioning.
See also: p10003 (SI TM54F forced checking procedure timer)
Remedy:
Carry out the forced checking procedure for the digital inputs/outputs.
The signal source to select the forced checking procedure is set via binector input p10007.
See also: p10007 (SI TM54F forced checking procedure F-DI/F-DO signal source)
A35015
TM54F: Motor/Hydraulic Module replaced or configuration inconsistent
Message value:
Fault cause: %1 bin
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
B_INF, TM54F_MA, TM54F_SL, VECTOR_G
Component:
None
Reaction:
NONE
Acknowledge:
NONE
Cause:
Cyclic communication of at least one drive with the Terminal Module 54F (TM54F) is not active.
Possible causes:
- at least one Motor Module/Hydraulic Module was replaced (e.g. hardware was replaced).
- the parameterization of theTM54F (p10010) is inconsistent with the number of drives, which have drive-based
motion monitoring functions activated with TM54F.
- For the signaled drive, it is not permissible that the "Safe motion monitoring without selection" (p9601.5 = 1) is
parameterized.
- And activated drive has no communication via DRIVE-CLiQ.
- p10010 of the TM54F master module is not the same as p10010 of the TM54F slave module (in this case, F35051
is also output).
- in p10010 of the TM54F master or slave module, the number of a drive object was entered several times.
- the control of the Basis Functions via TM54F was parameterized, and simultaneously the Extended Safety
Functions or ncSI were parameterized.
1872
Propagation:
GLOBAL
Propagation:
GLOBAL
List Manual (LH2), 07/2016, A5E03263479A