A35075 (F)
TM54F: Error during internal communication
Message value:
%1
Message class:
Hardware/software error (1)
Drive object:
B_INF, TM54F_MA, TM54F_SL, VECTOR_G
Component:
Terminal Module (TM)
Reaction:
NONE
Acknowledge:
NONE
Cause:
An internal communications error has occurred in the Terminal Module 54F (TM54F).
This message is also output in the following cases:
- parameter p10000 (TM54F master) is not set the same as p10000 (TM54F slave).
- parameter p10010 (TM54F master) is not set the same as p10010 (TM54F slave).
Alarm value (r2124, interpret decimal):
Only for internal Siemens diagnostics.
Remedy:
For p10010/p10000 from the TM54F master not equal to the TM54F slave:
- start the copy function for the node identifier on the TM54F (p9700 = 1D hex).
- acknowledge the hardware CRC on the TM54F (p9701 = EC hex).
- save all parameters (p0977 = 1).
- carry out a POWER ON (switch-off/switch-on) for all components.
For internal communication errors:
- check the electrical cabinet design and cable routing for EMC compliance
- upgrade the software on the TM54F.
- contact Technical Support.
- replace the TM54F.
Reaction upon F:
NONE
Acknowl. upon F:
IMMEDIATELY (POWER ON)
A35080 (F)
TM54F: Checksum error safety parameters
Message value:
%1
Message class:
Safety monitoring channel has identified an error (10)
Drive object:
B_INF, TM54F_MA, TM54F_SL, VECTOR_G
Component:
Terminal Module (TM)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The calculated checksum entered in r10004 over the safety-relevant parameters does not match the reference
checksum saved in p10005 at the last machine acceptance.
Fault value (r0949, interpret binary):
Bit 0 = 1: Checksum error for functional SI parameters.
Bit 1 = 1: Checksum error for SI parameters for component assignment.
Remedy:
- check the safety-relevant parameters and if required, correct.
- set the reference checksum to the actual checksum.
- acknowledge the hardware replacement.
- carry out a POWER ON (switch off/on).
- carry out an acceptance test.
Reaction upon F:
NONE
Acknowl. upon F:
IMMEDIATELY (POWER ON)
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Propagation:
GLOBAL
Propagation:
GLOBAL
4 Faults and alarms
4.2 List of faults and alarms
1877