4 Faults and alarms
4.2 List of faults and alarms
F34950
VSM: Internal software error
Message value:
%1
Message class:
Hardware/software error (1)
Drive object:
B_INF, VECTOR_G
Component:
Voltage Sensing Module (VSM)
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
An internal software error in the Voltage Sensing Module (VSM) has occurred.
Fault value (r0949, interpret decimal):
Information about the fault source.
Only for internal Siemens troubleshooting.
Remedy:
- if necessary, upgrade the firmware in the Voltage Sensing Module to a later version.
- contact Technical Support.
A34999 (F, N)
VSM: Unknown alarm
Message value:
New message: %1
Message class:
Infeed faulted (13)
Drive object:
B_INF, VECTOR_G
Component:
Voltage Sensing Module (VSM)
Reaction:
NONE
Acknowledge:
NONE
Cause:
A fault occurred on the Voltage Sensing Module (VSM) an alarm has occurred that cannot be interpreted by the
Control Unit firmware.
This can occur if the firmware on this component is more recent than the firmware on the Control Unit.
Alarm value (r2124, interpret decimal):
Alarm number.
Note:
If required, the significance of this new alarm can be read about in a more recent description of the Control Unit.
Remedy:
- replace the firmware on the Voltage Sensing Module by an older firmware version (r0148).
- upgrade the firmware on the Control Unit (r0018).
Reaction upon F:
Vector: NONE (OFF1, OFF2, OFF3)
Infeed: NONE (OFF1, OFF2)
Acknowl. upon F:
IMMEDIATELY (POWER ON)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
F35000
TM54F: Sampling time invalid
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
B_INF, TM54F_MA, TM54F_SL, VECTOR_G
Component:
None
Reaction:
NONE
Acknowledge:
POWER ON
Cause:
The set sampling time is invalid.
- not a multiple integer of the DP clock cycle.
Fault value (r0949, floating point):
Recommended valid sampling time.
Remedy:
Adapt the sampling time (e.g. set the recommended valid sampling time).
See also: p10000 (SI TM54F communication clock cycle)
1866
Propagation:
LOCAL
Propagation:
LOCAL
Propagation:
GLOBAL
List Manual (LH2), 07/2016, A5E03263479A