Fault value (r0949, interpret hexadecimal):
aaaabbcc hex:
aaaa: DO or F-DI (dependent on test step cc), where the expected state was not assumed (bit 0 = F-DI 0 or F-DO 0,
bit 1 = F-DI 1 or F-DO 1, etc.).
bb: Fault cause
bb = 01 hex: Internal fault.
bb = 02 hex: Fault when comparing the switching signals of the two channels (F-DI or DI).
bb = 03 hex: Internal fault.
bb = 04 hex: Fault when comparing the switching signals of the two channels (Diag-DO).
cc: State of the test stop in which the fault has occurred.
The display format is as follows:
Slave fault state: (test actions)(test actions) | corresponding step for the master: (test actions)(test actions) |
Description
00 hex: (L1+OFF)(L2+ON) | 0A hex: ( )( ) | Synchronization / switching step
0A hex: (L1+OFF)(L2+ON) | 15 hex: ( )( ) | Wait step
15 hex: (L1+OFF)(L2+OFF) | 20 hex:( )( ) | 1.) F-DI 0 ... 4 check for 0 V 2.) Switch step to new level
20 hex: (L1+OFF)(L2+OFF) | 2B hex: ( )( ) | Wait step
2B hex: (L1+ON)(L2+ON) | 36 hex: ( )( ) | 1.) F-DI 5 ... 9 check for 0 V 2.) Switch step to new level
36 hex: (DO OFF)( ) | 41 hex: (DO OFF)( ) | Wait step / switching step
41 hex: (DO OFF)( ) | 4C hex: (DO OFF)( ) | Wait step
4C hex: (DO ON)( ) | 57 hex: (DO ON)( ) | 1.) Check diag-DO or diag-DI 2.) Switch step to new level
57 hex: (DO ON)( ) | 62 hex: (DO ON)( ) | Wait step
62 hex: (DO OFF)( ) | 6D hex: (DO ON)( ) | 1.) Check diag-DO or diag-DI 2.) Switch step
6D hex: (DO OFF)( ) | 78 hex: (DO ON)( ) | Wait step
78 hex: (DO ON)( ) | 83 hex: (DO OFF)( ) | 1.) Check diag-DO or diag-DI 2.) Switch step
83 hex: (DO ON)( ) | 8E hex: (DO OFF)( ) | Wait step
8E hex: (DO OFF)( ) | 99 hex: (DO OFF)( ) | 1.) Check diag-DO or diag-DI 2.) Switch step
99 hex: (DO OFF)( ) | A4 hex: (DO OFF)( ) | Wait step
A4 hex: (DO OFF)( ) | AF hex: (DO OFF)( ) | Check Diag-DO or Diag-DI
AF hex: (DO original state)() | C5 hex: (DO original state)() | Switching step
C5 hex: End of test
The expected states to be checked depend on the parameterized test mode (p10047).
The following expected states are tested in the test steps when testing the F-DOs:
The display format is as follows:
Test step (SL MA): Expected Diag-DO mode 1 | Expected DI 20 ... 23 mode 2 | Expected DI 20 ... 23 mode 3
(4C hex 57 hex): Diag-DO = 0 V | DI = 24 V | DI = 24 V
(62 hex 6D hex): Diag-DO = 0 V | DI = 0 V | DI = 0 V
(78 hex 83 hex): Diag-DO = 0 V | DI = 0 V | DI = 24 V
(8E hex 99 hex): Diag-DO = 24 V | DI = 0 V | DI = 24 V
(A4 hex AF hex): Diag-DO = 0 V | DI = 24 V | DI = 24 V
Example:
If an error with fault causes bb = 02 hex or 04 hex occurs in a test stop step, the test action for the fault took place in
the previous test stop step. The expected states are tested in the next step.
Master signals fault value 0001_04AF and slave signals fault value 0001_04A4.
aaaa = 1 --> F-DO 0 is involved.
bb = 04 hex --> the test of the Diag-DO was unsuccessful.
cc = The expected states were tested in test stop step AF on the master and A4 on the slave.
The expected state Diag-DO = 0 V was checked in the table, i.e. Diag-DO was at 0 V instead of the expected 24 V.
The associated test action took place in the previous step (99 hex DO OFF, A4 hex DO OFF). Both DOs were
switched to OFF.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
4 Faults and alarms
4.2 List of faults and alarms
1871