8-1-1

Safety Input Signals

There are 2 safety input circuits to operate the STO function.
Signal
Symbol
name
Safety
SF
input 1
SF
Safety
SF2
input 2
SF2
• When safety input 1 or 2 turns "OFF," the STO function will start operating within 5 ms of the input,
and the motor output torque will be reduced to 0.
• Connect the equipment so that the safety input circuit is turned OFF to operate the STO function.
• Set the operation when the safety input turns "OFF" in the Fault reaction option code (605E hex).
Precautions for Correct Use
Precautions for Correct Use
L pulses for self-diagnosis of safety equipment
When you are connecting a safety device, such as a safety controller or a safety sensor, the
safety output signal of the device may include L pulses for self-diagnosis. To avoid
malfunction due to the L pulses for self-diagnosis, a filter that removes the L pulses is built
into the safety input circuit. If the OFF time of the safety input signal is 1 ms or less, the
safety input circuit does not recognize it as "OFF." To make sure that "OFF" is recognized,
maintain the OFF status of safety input signal for at least 5 ms.
Safety input signal
Servo Drive
operation
G5 Series AC Servo Drives With Built-in EtherCAT Communications, Linear Motor Type
Pin
Description
number
CN8-4
The upper arm drive signal of the power
transistor inside the Servo Drive is cut
off.
CN8-3
CN8-6
The lower arm drive signal of the power
transistor inside the Servo Drive is cut
off.
CN8-5
For self-diagnosis
Within 1 ms
Normal operation
Position
L pulse
5 ms or more
Within 5 ms
STO status
8 Safety Function
Control mode
Speed
Force
8-3
8