Appendicies
Event name
Object Corrupted
Meaning
The checksum data in non-volatile memory is corrupted.
Source
EtherCAT Master Function Module
Error attributes
Level
Effects
User program
Indicators
EtherNet/IP NET RUN
---
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
Non-volatile memory failure
Attached
None
information
Precautions/
"37" is displayed on the Servo Drive front panel and F237 is given as the AlarmCode (4001 hex).
Remarks
Event name
Motor Setting Error
Meaning
Settings associated with the motor and external encoder are missing.
Source
EtherCAT Master Function Module
Error attributes
Level
Effects
User program
Indicators
EtherNet/IP NET RUN
---
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
Settings associated with the motor
and external encoder are missing.
Attached
None
information
Precautions/
"50" is displayed on the Servo Drive front panel and F060 is given as the AlarmCode (4001 hex).
Remarks
A-122
Source details
Minor fault
Recovery
Continues.
Operation
EtherNet/IP NET ERR
---
Data type
---
Remedy
Replace the Servo Drive.
Source details
Minor fault
Recovery
Continues.
Operation
EtherNet/IP NET ERR
---
Data type
---
Remedy
Check the specifications of the motor
and external encoder and provide the
required settings.
G5 Series AC Servo Drives With Built-in EtherCAT Communications, Linear Motor Type
Event code
14AD0000 hex
Slave
Detection
timing
Error reset (after
Log category
cycling slave
power)
Power drive circuit is OFF for relevant slave.
EtherNet/IP LINK/ACT
---
Name
---
Prevention
None
Event code
28010000 hex
Slave
Detection
timing
Error reset (after
Log category
cycling slave
power)
Power drive circuit is OFF for relevant slave.
EtherNet/IP LINK/ACT
---
Name
---
Prevention
Check the specifications of the motor
and external encoder and provide the
required settings.
When
establishing
communications
after turning ON
power to the
slave
System
Continuously
System

Hide quick links: