Omron R88D-KN series User Manual page 551

G5-series with built-in ethercat communications linear motor type
Hide thumbs Also See for R88D-KN series:
Table of Contents

Advertisement

Event name
Communications Setting Error
Meaning
There is an error in the communications settings.
Source
EtherCAT Master Function Module
Error attributes
Level
Effects
User program
Indicators
EtherNet/IP NET RUN
---
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
An out-of-range value was set from
the host controller.
A command that changes the
communications state to an
unsupported state was received.
Attached
None
information
Precautions/
"90" is displayed on the Servo Drive front panel and F090 is given as the AlarmCode (4001 hex).
Remarks
Event name
Synchronization Interruption Error
Meaning
A synchronization interruption error occurred.
Source
EtherCAT Master Function Module
Error attributes
Level
Effects
User program
Indicators
EtherNet/IP NET RUN
---
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
Control PCB error
Attached
None
information
Precautions/
"88" is displayed on the Servo Drive front panel and F288 is given as the AlarmCode (4001 hex)
Remarks
G5 Series AC Servo Drives With Built-in EtherCAT Communications, Linear Motor Type
Source details
Minor fault
Recovery
Continues.
Operation
EtherNet/IP NET ERR
Flashes at 1-s intervals.
Data type
---
Remedy
Set EtherCAT communications
parameters so that the synchronous
cycle (SYNC0 cycle) and other setting
are within the specified ranges.
Check the command specifications
for communications state transitions
in the host controller and correct host
controller processing.
Source details
Minor fault
Recovery
Continues.
Operation
EtherNet/IP NET ERR
Flashes at 1-s intervals.
Data type
---
Remedy
Replace the Servo Drive.
Event code
84B80000 hex
Slave
Detection
timing
Error reset (after
Log category
resetting slave
errors)
Power drive circuit is OFF for relevant slave.
EtherNet/IP LINK/ACT
---
Name
---
Prevention
Set EtherCAT communications
parameters so that the synchronous
cycle (SYNC0 cycle) and other setting
are within the specified ranges.
Check the command specifications
for communications state transitions
in the host controller and program
host controller processing.
Event code
84B90000 hex
Slave
Detection
timing
Error reset (after
Log category
cycling slave
power)
Power drive circuit is OFF for relevant slave.
EtherNet/IP LINK/ACT
---
Name
---
Prevention
None
Appendicies
Continuously
System
Continuously
System
A-151

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents