Appendicies
Event name
External Encoder Connection Error
Meaning
A disconnection was detected because communications between the external encoder and the Servo Drive were
stopped more frequently than the specified value.
Source
EtherCAT Master Function Module
Error attributes
Level
Effects
User program
Indicators
EtherNet/IP NET RUN
---
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
The wiring is incorrect.
Attached
None
information
Precautions/
"50" is displayed on the Servo Drive front panel and F050 is given as the AlarmCode (4001 hex).
Remarks
Event name
External Encoder Communications Data Error
Meaning
There was a communications error in data from the external encoder.
Source
EtherCAT Master Function Module
Error attributes
Level
Effects
User program
Indicators
EtherNet/IP NET RUN
---
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
There is insufficient external encoder
power supply voltage.
Noise
Attached
None
information
Precautions/
"50" is displayed on the Servo Drive front panel and F150 is given as the AlarmCode (4001 hex).
Remarks
A-114
Source details
Minor fault
Recovery
Continues.
Operation
EtherNet/IP NET ERR
---
Data type
---
Remedy
Wire the external encoder correctly as
shown in the wiring diagram. Correct
the connector pin connections.
Source details
Minor fault
Recovery
Continues.
Operation
EtherNet/IP NET ERR
---
Data type
---
Remedy
Provide the required external encoder
power supply voltage 5 VDC 5%
(4.75 to 5.25 V).
If the motor cable and the external
encoder cable are bundled together,
separate them. Connect the shield to
FG.
G5 Series AC Servo Drives With Built-in EtherCAT Communications, Linear Motor Type
Event code
080C0000 hex
Slave
Detection
timing
Error reset (after
Log category
cycling slave
power)
Power drive circuit is OFF for relevant slave.
EtherNet/IP LINK/ACT
---
Name
---
Prevention
Wire the external encoder correctly as
shown in the wiring diagram. Connect
the connector pins correctly.
Event code
080D0000 hex
Slave
Detection
timing
Error reset (after
Log category
cycling slave
power)
Power drive circuit is OFF for relevant slave.
EtherNet/IP LINK/ACT
---
Name
---
Prevention
Provide the required external encoder
power supply voltage 5 VDC 5%
(4.75 to 5.25 V).
If the motor cable and the external
encoder cable are bundled together,
separate them. Connect the shield to
FG.
Continuously
System
Continuously
System