Safety Input Units

Number
Appearance
of safety
input
points
4 points
8 points

Safety Output Units

Number
Appearance
of safety
output
points
Sourcing out-
2 points
puts
(PNP)
Sourcing out-
4 points
puts
(PNP)
Number
Rated
of test
Internal I/O
input
output
common
voltage
points
Sinking inputs
2 points
24 VDC
(PNP)
Sinking inputs
2 points
24 VDC
(PNP)
Internal
Maximum load current
I/O common
2.0 A/point, 4.0 A/Unit at 40°C, and 2.5
A/Unit at 55°C
The maximum load current depends on
the installation orientation and ambient
temperature.
0.5 A/point and 2.0 A/Unit
Machine Automation Controller
Specifications
Number of
OMRON special
safety slave
safety input devices
connections
Can be connected.
1
Cannot be connected.
1
Specifications
Number of
Rated
safety slave
voltage
connections
24 VDC
1
24 VDC
1
I/O
Model
Unit
refreshing
version
method
Free-Run
Ver.1.1
NX-SIH400
refreshing
Free-Run
Ver.1.0
NX-SID800
refreshing
I/O
Model
Unit
refreshing
version
method
Free-Run
Ver.1.0
NX-SOH200
refreshing
Free-Run
Ver.1.0
NX-SOD400
refreshing
NX1