Servo Drive model
R88D-KN06F-ECT-L
R88D-KN10F-ECT-L
R88D-KN15F-ECT-L
R88D-KN20F-ECT-L
R88D-KN30F-ECT-L
R88D-KN50F-ECT-L
R88D-KN75F-ECT-L
R88D-KN150F-ECT-L
Note These values vary greatly depending on the installation conditions of the motor power cable and the
measurement conditions. Use the values for reference only.
Surge Absorber
• Use surge absorbers to absorb lightning surge voltage and abnormal voltage from power supply input
lines.
• When selecting surge absorbers, take into account the varistor voltage, the surge immunity and the
energy tolerated dose.
• For 200-VAC systems, use surge absorbers with a varistor voltage of 620 V.
The surge absorbers shown in the following table are recommended.
Manufacturer
Okaya Electric
Industries Co., Ltd.
Okaya Electric
Industries Co., Ltd.
Okaya Electric
Industries Co., Ltd.
Note 1 Refer to the manufacturers' catalog for operating details.
2 The surge immunity is for a standard impulse current of 8/20 s. If pulses are wide, either decrease the
current or change to a larger-capacity surge absorber.
G5 Series AC Servo Drives With Built-in EtherCAT Communications, Linear Motor Type
Input power supply
3-phase 400 V
3-phase 400 V
3-phase 400 V
3-phase 400 V
3-phase 400 V
3-phase 400 V
3-phase 400 V
3-phase 400 V
Model
Surge immunity
700 V  20%
R·A·V-781BWZ-4
700 V  20%
R·A·V-781BXZ-4
800V  20%
R·A·V-801BXZ-4
4 System Design
Leakage current
(Cable: 3 m)
2.28 mA
2.20 mA
2.55 mA
2.92 mA
3.92 mA
3.54 mA
6.70 mA
10.40 mA
Type
2500 A
Block
2500 A
2500 A
Increase per 10 m
of cable
1.8 mA
2.03 mA
2.4 mA
3.23 mA
2.9 mA
3.73 mA
2.73 mA
Comment
Single-phase
100/200 VAC
3-phase 200 VAC
3-phase 400 VAC
4-41