Event name
Regeneration Overload
Meaning
The regenerative energy exceeds the processing capacity of the Regeneration Resistor.
Source
EtherCAT Master Function Module
Error attributes
Level
Effects
User program
Indicators
EtherNet/IP NET RUN
---
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
The load mass is too large. Or, the
motor speed is too high to absorb the
regenerative energy within the
specified deceleration time.
This Regeneration Resistor cannot be
used for continuous regenerative
braking. (The operating limit of the
external resistor is limited to a 10%
duty.)
Attached
None
information
Precautions/
"18" is displayed on the Servo Drive front panel and F018 is given as the AlarmCode (4001 hex)
Remarks
G5 Series AC Servo Drives With Built-in EtherCAT Communications, Linear Motor Type
Source details
Minor fault
Recovery
Continues.
Operation
EtherNet/IP NET ERR
---
Data type
---
Remedy
Check the operation pattern (velocity
monitor). Check the Regeneration
Register load rate and the excessive
regeneration warning, and perform
the following accordingly.
• Increase the capacity of the motor
and Servo Drive.
• Increase the deceleration time.
• Reduce the motor speed.
• Use an External Regeneration
Resistor.
• Set the Regeneration Resistor
Selection (3016 hex) to 2.
Set the Regeneration Resistor
Selection (3016 hex) to 2.
Event code
34E30000 hex
Slave
Detection
timing
Error reset (after
Log category
cycling slave
power)
Power drive circuit is OFF for relevant slave.
EtherNet/IP LINK/ACT
---
Name
---
Prevention
Check the items given for corrections
in advance and implement
countermeasures as required.
Set the Regeneration Resistor
Selection (3016 hex) to 2.