22.3 GOT Side Settings

22.3.1
Setting communication interface
(Communication settings)
Set the channel of the connected equipment.
2.
1.
Select [Common]
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: Mitsubishi
• Controller Type: Set according to the Controller
Type to be connected.
• I/F: Interface to be used
• Driver:
Ethernet(MELSEC), Q17nNC, CRnD-700
Ethernet(FX), Gateway
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.
22.3.2 Communication detail settings
Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
17.1.2 I/F communication setting
22 - 14
22. ETHERNET CONNECTION
22.3 GOT Side Settings
Click!
[Controller Setting] from the
22.3.2 Communication detail settings
Make the settings according to the usage environment.
Item
GOT NET No.
*3
GOT PLC No.
GOT
*2
IP Address
3.
*2
Subnet Mask
4.
Default
*2
Gateway
Ethernet
Download Port
*2
No.
GOT
Communication
Port No.
Retry
Startup Time
*1
Timeout time
Delay Time
*1
To connect the GOT with the Ethernet module (Q Series) in
the one-on-one relationship using a cross cable,
set [Timeout Time] to 6 sec. or longer.
*2
Click the [Setting] button and perform the setting in the [GOT
IP Address Setting] screen.
*3
Each of [GOT PLC No.] set in the communication detail
setting and [PLC No.] set in the Ethernet setting must be set
to different station numbers.
*4
When the drive is [Ethernet(FX), Gateway] , the range is 1 to 64.
Description
Set the network No. of the GOT.
(Default: 1)
Set the station No. of the GOT.
(Default: 1)
Set the IP address of the GOT.
(Default: 192.168.3.18)
Set the subnet mask for the sub
network. (Only for connection via
router)
If the sub network is not used, the
default value is set.
(Default: 255.255.255.0)
Set the router address of the default
gateway where the GOT is connected.
(Only for connection via router)
(Default: 0.0.0.0)
Set the GOT port No. for Ethernet
download.
(Default: 5014)
Set the GOT port No. for the
connection with the Ethernet module.
For Ethernet(MELSEC), Q17nNC
and CRnD-700
(default: 5001)
For Ethernet (FX), Gateway
(default: 5019)
Set the number of retries to be
performed when a communication
timeout occurs.
When receiving no response after
retries, the communication times out.
(Default: 3times)
Specify the time period from the GOT
startup until GOT starts the
communication with the PLC CPU.
(Default: 3sec)
Set the time period for a
communication to time out.
(Default: 3sec)
Set the delay time for reducing the
load of the network/destination PLC.
(Default: 0ms)
22.3.3 Ethernet setting
Range
1 to 239
*4
1 to 120
0.0.0.0 to
255.255.255.255
0.0.0.0 to
255.255.255.255
0.0.0.0 to
255.255.255.255
1024 to 5010,
5014 to 65534
(Except for 5011, 5012,
5013 and 49153)
1024 to 5010,
5014 to 65534
(Except for 5011, 5012,
5013 and 49153)
0 to 5times
3 to 255sec
3 to 90sec
0 to 10000
( 10 ms)