PLC
Ethernet module
Model name
*3*4
AJ71E71N3-T
AJ71E71N-B5
AJ71E71N-B2
MELSEC-A
AJ71E71N-T
AJ71E71N-B5T
MELSEC-Q
AJ71E71-S3
(A mode)
A1SJ71E71N3-T
A1SJ71E71N-B5
Motion
A1SJ71E71N-B2
controller
A1SJ71E71N-T
CPU (A Series)
A1SJ71E71N-B5T
A1SJ71E71-B5-S3
A1SJ71E71-B2-S3
MELSEC-L
LJ71E71-100
*1
The destination connected with the twisted pair cable varies with the configuration of the applicable Ethernet network system.
Connect to the Ethernet module, hub, transceiver, or other system equipment corresponding to the applicable Ethernet network
system.
Use cables, connectors, and hubs that meet the IEEE802.3 10BASE-T/100BASE-TX standard.
A cross cable is available for connecting the GOT to the Ethernet module.
The use of shielded twisted pair cable (STP) is recommended in environments in which the performance against noise is
required.
*2
A length between a hub and a node.
The maximum distance differs depending on the Ethernet device to be used.
The following shows the number of the connectable nodes when a repeater hub is used.
• 10BASE-T: Max. 4 nodes for a cascade connection (500m)
• 100BASE-TX: Max. 2 nodes for a cascade connection (205m)
When switching hubs are used, the cascade connection between the switching hubs has no logical limit for the number of
cascades.
For the limit, contact the switching hub manufacturer.
*3
For the system configuration of the Ethernet module, refer to the following manuals.
*4
Select one of the following [Controller Type] in [Ethernet] of GT Designer3.
• Ethernet module (MELSEC iQ-R Series): RJ71EN71
• Ethernet module (Q Series): QJ71E71
• Ethernet module (QnA Series): AJ71QE71
• Ethernet module (A Series): AJ71QE71
For [Ethernet] of GT Designer3, refer to the following.
*5
When using the peripheral I/F of Q170MCPU, Q17nDCPU-S1 or MR-MQ100, refer to the following.
*6
The number of connectable GOTs for one network is 63 units (at most).
22 - 6
22. ETHERNET CONNECTION
22.2 System Configuration
Connection cable
Communication
Cable model
Type
• 10BASE-T
Shielded twisted pair
cable (STP) or
unshielded twisted
pair cable (UTP) :
Ethernet
Category 3, 4, and 5
100BASE-TX
Shielded twisted pair
cable (STP) : Category
5 and 5e
Q Corresponding Ethernet Interface Module User's Manual (Basic)
For QnA Ethernet Interface Module User's Manual
For A Ethernet Interface Module User's Manual
22.3.3 Ethernet setting
22.2.5 Connecting to PERIPHERAL I/F
Connector
External cable
conversion box
*1
GT16H-C30-42P(3m)
GT16H-CNB-42S
GT16H-C60-42P(6m)
GT16H-C100-42P(10m)
GT16H-C30-37PE(3m)
GT16H-CNB-37S
GT16H-C60-37PE(6m)
GT16H-C100-37PE(10m)
GT16H-C30-42P(3m)
GT16H-CNB-42S
GT16H-C60-42P(6m)
GT16H-C100-42P(10m)
GT16H-C30-37PE(3m)
GT16H-CNB-37S
GT16H-C60-37PE(6m)
GT16H-C100-37PE(10m)
Maximum
Number of
GOT
segment
connectable
model
*2
equipment
length
*6
128 GOTs
(recommended
100m
to 16 units or
less)