Mitsubishi Electric GT16 User Manual page 950

Got1000 series
Hide thumbs Also See for GT16:
Table of Contents

Advertisement

(a) Setting of the MODE
Make the MODE settings using the MODE switch.
MODE
NV1L-RS2
Command-setting-type
start-stop
synchronization,
nonsequence format
(b) Setting of Transmission speed, Stop bit, Data bit,
Parity bit, Initializing method
For the NV1L-RS2
For the NC1L-RS2
Setting item
Set value
1
9600bps
ON OFF ON
Transmission
speed
19200bps
OFF ON
1bit
Stop bit
2bits
7bits
Data bit
8bits
Even
Odd
Parity bit
Done
None
Initializing
By switch
method
47 - 14
47. CONNECTION TO FUJI PLC
47.2 Serial Connection
Switch position
NC1L-RS2
1
1
Switch No.
2
3
4
5
6
ON
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Connecting to NC1L-RS4
(1) Communication settings
Make the communication settings using setting switches.
Item
MODE
Transmission speed
*1
Data bit
*1
Parity bit
*1
Stop bit
Initializing method
*1*2
Station No.
Terminating resistor
*1
*2
*3
(2) Settings by switch
Make the communication settings using each setting switch.
7
8
RS-485 station No.
switches
(a) Setting of the MODE
Make the MODE settings using the MODE switch.
Command-setting-type start-stop
ON
synchronization, nonsequence
(b) Setting of the station No.
Make the station No. using RS-485 station No.
switches.
Station No.
(c) Connecting terminating resistors
Turn ON/OFF the terminating resistor using RS-
485 terminating resistor ON/OFF switch.
Set value
Command-setting-type start-stop
synchronization, nonsequence format
*1
9600bps, 19200bps
8bits or 7bits
Even or Odd
Done, None
1bit, 2bits
By switch
0 to 99
*3
ON or OFF
Adjust the settings with GOT settings.
Avoid duplication of the station No. with any of the other
units.
Turn ON the terminating switch of a general-purpose
interface module which will be a terminal.
(Front view) (Rear view)
MODE
Switch position
3
format
0 to 99
ON
Character configuration
switches
Terminator switch
MODE switch