24.5.3 Connecting FREQROL-F500,
F500L series
Communication settings
Make the communication settings of the inverter.
Be sure to perform the inverter reset after updating
each parameter.
(1) Communication port and corresponding parameters
GOT connection destination
Parameters corresponding to inverter
PU connector
FR-A5NR (Option unit)
Pr.79, Pr.331 to Pr.337, Pr.340 to Pr.342
(2) Communication settings of inverter
Set the following parameters using the PU (parameter
unit). Set Pr.160 (user group read selection) to 0 [All
parameters can be accessed for reading and writing.]
before making the parameter settings.
Do not change these parameters, even though they
can be monitored from the GOT. If they are changed,
communication with the GOT is disabled.
Parameter No.
*1
Setting item
PU
FR-
connector
A5NR
Communication
Pr.117
Pr.331
station number
Communication
Pr.118
Pr.332
*2
speed
Stop bit length/data
length
Pr.119
Pr.333
*2
Stop bit length
Parity check
Pr.120
Pr.334
*2
presence/absence
Number of
Pr.121
Pr.335
communication retries
Communication check
Pr.122
Pr.336
time interval
Wait time setting
Pr.123
Pr.337
CRLF presence/
Pr.124
Pr.341
absence selection
*5
-
-
Protocol selection
Operation mode
Pr.79
selection
Link start mode
-
Pr.340
*6
selection
2
E
PROM
-
Pr.342
*6
write selection
*1
Setting items are parameter names described in the manual
of FREQROL-F500 and F500L series.
*2
Settings on the GOT can be changed.
When changing the settings on the GOT, be sure to change
the parameters on the inverter to correspond with the GOT
settings.
*3
Inverter default values (No need to change)
*4
Since the value has been set as a default, no setting is
required when connecting to the PU connector on the
inverter side.
*5
There is no Protocol selection setting on the inverter side.
*6
The setting is required on the inverter side when FR-A5NR is
used.
Pr.79, Pr.117 to Pr.124
Contents of
Set value
setting
0 to 31
24.5.13 Station
number setting
*4
19200bps
192
Data length: 7bit
10
Stop bit length:
1bit
1
Odd
The inverter will
9999
not come to an
alarm stop.
Communication
9999
check suspension
0
0ms
With CR
*3
1
Without LF
-
-
PU
PU operation
1
connector
mode
External
*3
FR-A5NR
operation
0
mode at power on
Computer link
1
operation
Written to RAM
*3
0
and EEPROM
24.5.4 Connecting FREQROL-A500,
A500L series
Communication settings
Make the communication settings of the inverter.
Be sure to perform the inverter reset after updating
each parameter.
(1) Communication port and corresponding parameters
GOT connection destination
PU connector
FR-A5NR (Option unit)
(2) Communication settings of inverter
Set the following parameters using the PU (parameter
unit). Do not change these parameters, even though they
can be monitored from the GOT. If they are changed,
communication with the GOT is disabled.
Parameter No.
*1
Setting item
PU
connector
Communication
Pr.117
station number
Communication
Pr.118
*2
speed
*2
Pr.119
Stop bit length
Parity check
Pr.120
presence/absence
*2
Number of
communication
Pr.121
retries
Communication
Pr.122
check time interval
Wait time setting
Pr.123
CRLF presence/
Pr.124
absence selection
*5
-
Protocol selection
Operation mode
Pr.79
selection
Link start mode
-
*6
selection
2
E
PROM
Pr.342
write selection
*1
Setting items are parameter names described in the manual
of FREQROL-A500 and A500L series.
*2
Settings on the GOT can be changed.
When changing the settings on the GOT, be sure to change
the parameters on the inverter to correspond with the GOT
settings.
*3
Inverter default values (No need to change)
*4
Since the value has been set as a default, no setting is
required when connecting to the PU connector on the
inverter side.
*5
There is no Protocol selection setting on the inverter side.
*6
The setting is required on the inverter side when FR-A5NR is
used.
24. INVERTER CONNECTION
24.5 FREQROL Series Inverter Side Settings
Parameters corresponding to inverter
Pr.79, Pr.117 to Pr.124, Pr.342
Pr.79, Pr.331 to Pr.337, Pr.340 to Pr.342
Set value
Contents of setting
FR-
A5NR
Pr.331
0 to 31
24.5.13 Station
number setting
Pr.332
*4
19200bps
192
Data length: 7bit
Pr.333
10
Stop bit length: 1bit
Pr.334
1
Odd
The inverter will not
Pr.335
9999
come to an alarm
stop.
Communication
Pr.336
9999
check suspension
Pr.337
0
0ms
With CR
*3
Pr.341
1
Without LF
-
-
-
PU
PU operation mode
1
connector
External operation
FR-A5NR
*3
0
mode at power on
Computer link
Pr.340
1
operation
Written to RAM and
*3
0
EEPROM
24 - 17