40.5 Controller Side Setting

POINT
POINT
POINT
(1) CHINO controller
For details of CHINO controller, refer to the
following manual.
User's Manual of the CHINO controller
(2) Converter
For details on communication settings of the
communication converter, refer to the following
manual.
User's Manual for converter
Model name
LT230, LT300
LT400, LT830
DZ1000, DZ2000
DB1000, DB2000
GT120
KP1000, KP2000
Controller
AL3000, AH3000
SE3000
JU
KE3000
LE5100, LE5200,
LE5300
Converter
SC8-10
40.5.1 Connecting to LT230, LT300
Series
Key Lock setting
To write the Digital and the Analog parameters, set the
Key Lock setting to Lock 4.
Communication settings
Set the communication settings with controller key
operation.
Item
Protocol
Function
*1
Station No.
*2
Transmission speed
*2
Character
(Bit length, Parity bit, Stop bit)
*1
Avoid duplication of the station No. with any of the other
units.
*2
Adjust the settings with GOT settings.
40 - 12
40. CONNECTION TO CHINO CONTROLLER
40.5 Controller Side Setting
Refer to
40.5.1
40.5.2
40.5.3
40.5.4
40.5.5
40.5.6
40.5.7
40.5.8
40.5.9
40.5.10
40.5.11
40.5.12
Set value
rtU: MODBUS RTU
Com: Upper communication
1 to 99
9600bps, 19200bps
5: 8bit, None, 1bit
6: 8bit, None, 2bit
7: 8bit, Even, 1bit
8: 8bit, Even, 2bit
9: 8bit, Odd, 1bit
10: 8bit, Odd, 2bit
40.5.2 Connecting to LT400, LT830
Series
Key Lock setting
To write the Digital and the Analog parameters, set the
following Key Lock setting
• LT400: Lock4
• LT830: Lock3
Communication settings
Set the communication settings with controller key
operation.
Item
Protocol
Function
*1
Station No.
*2
Transmission speed
*2
Character
(Bit length, Parity bit, Stop bit)
*1
Avoid duplication of the station No. with any of the other
units.
*2
Adjust the settings with GOT settings.
40.5.3 Connecting to DZ1000,
DZ2000 Series
Key Lock setting
To write the Digital and the Analog parameters, set the
Key Lock setting to Lock 2.
Communication settings
Set the communication settings with controller key
operation.
Item
Protocol
Function
*1
Station No.
*2
Transmission speed
Data bit
Stop bit
Parity bit
*1
Avoid duplication of the station No. with any of the other
units.
*2
Adjust the settings with GOT settings.
Set value
rtU: MODBUS RTU
Com: Upper communication
1 to 99
9600bps, 19200bps
8N1: 8bit, None, 1bit
8N2: 8bit, None, 2bit
8E1: 8bit, Even, 1bit
8E2: 8bit, Even, 2bit
8O1: 8bit, Odd, 1bit
8O2: 8bit, Odd, 2bit
Set value
rtU: MODBUS RTU
Com: Upper communication
1 to 31
9600bps, 19200bps
8bits (fixed)
1bit (fixed)
None (fixed)