(For FUJI MICREX-SX SPH)
Item
Description
Set this item when change the
transmission speed used for
Transmission
communication with the connected
*1
Speed
equipment.
(Default: 38400bps)
Set this item when change the data
length used for communication with
*1
Data Bit
the connected equipment.
(Default: 8bits)
Set this item when change the data
length used for communication with
*1
Stop Bit
the connected equipment.
(Default: 1bit)
Specify whether or not to perform a
parity check, and how it is performed
*1
Parity
during communication.
(Default: Even)
Set the number of retries to be
performed when a communication
Retry
error occurs.
(Default: 3time)
Set the time period for a
Timeout Time
communication to time out.
(Default: 3sec)
Set this item to adjust the
transmission timing of the
Delay Time
communication request from the
GOT.
(Default: 0ms)
*1
Leave the setting as default. If the set value is changed,
communication with the PLC is disabled.
POINT
POINT
POINT
(1) Host Address
When connecting to PLC by RS-232
communication, set the Host Address to "0".
(2) Communication interface setting by the Utility
The communication interface setting can be
changed on the Utility's [Communication setting]
after writing [Communication Settings] of project
data.
For details on the Utility, refer to the following.
12. COMMUNICATION INTERFACE SETTING
(COMMUNICATION SETTING)
(3) Precedence in communication settings
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
47.2.7
Range
9600bps,
19200bps,
POINT
POINT
POINT
38400bps,
57600bps,
115200bps
FUJI PLC
For details of FUJI PLCs, refer to the following
manuals.
7bits/8bits
1bit/2bits
RS-232C interface card
None
General-purpose interface
Even
module
Odd
RS-232C/485 interface
capsule
0 to 5times
1 to 30sec
Connecting to NV1L-RS2, NC1L-RS2
(1) Communication settings
Make the communication settings using setting
0 to 300ms
switches.
Item
MODE
Transmission speed
*1
Data bit
*1
Parity bit
*1
Stop bit
Initializing method
*1
(2) Settings by switch
Make the communication settings using each setting
switch.
(For the NV1L-RS2)
(Front view)
47. CONNECTION TO FUJI PLC

PLC Side Setting

FUJI PLC user's Manual
Model name
NV1L-RS2
■ Connecting to NV1L-RS2,
NC1L-RS2
NC1L-RS2
NC1L-RS4
■ Connecting to NC1L-RS4
FFU120B
■ Connecting to FFU120B
■ Connecting to FFK120A-
FFK120A-C10
C10
Set value
Command-setting-type start-stop
synchronization, nonsequence format
*1
9600bps, 19200bps
8bits or 7bits
Even or Odd
Done, None
1bit, 2bits
By switch
Adjust the settings with GOT settings.
(For the NC1L-RS2)
Character configuration
switches
Operation mode
setting switch
(Front view)
(Rear view)
47.2 Serial Connection
44
45
Refer to
46
47
48
49
50
(Rear view)
51
47 - 13