28.6 Device Range that Can Be Set

Device setting items for GT Designer3
Item
Set the device name, device number, and bit number.
Device
The bit number can be set only when specifying the bit of
word device.
Displays the device type and its setting range selected in
Information
[Device].
Set the station number of the controller to be monitored.
Select this item for monitoring the host
Host
controller.
Select this item for monitoring other controllers.
Network
After selecting the item, set the station number
and network number of the controller to be
Other
monitored.
NW No.: Set [1].
Station No.: Set the station No.
Address
GT Designer3 converts the device numbers into
decimal format according to the address map of the
energy measuring unit/electric multi-measuring
instrument to be used.
The table below shows the representations on the
MODBUS/RTU communication protocol and GT
Designer3.
MODBUS/RTU Communication protocol
Function Code to
be used
Device name
Read
Write
Holding
0x03
0x10
register
28. ENERGY MEASURING UNIT/ELECTRIC MULTI-MEASURING INSTRUMENT CONNECTION
Description
Representation
Device name on GT
Address
Designer3
0000
400001
0001
400002
to
to
FFFE
465535
FFFF
465536
POINT
POINT
POINT
Address conversion example
For monitoring the address "031AH" of holding register
(Current value of total power)
The address of the holding register is displayed as
"4*****" on GT Designer3.
GT Designer3 converts the holding register's address
"031AH" to "00794" in decimal format.
Then, "+1" is added to this decimal address since the
holding register's address on GT Designer3 always
starts from "1."
Therefore, the holding register's address "031AH" is
displayed as "400795" on GT Designer3.
Holding register
"4
00794" +1
"400795"
GS device settings
Set the GS device as follows.
*1
GS573
= 2
*1
The GS device specifies the maximum number of the
holdingregister read times.
To input the numerical values to the GS device
automatically at GOT startup, use the status
observation function or the script function.
(Setting example of the status observation function)
For details of the status observation function or the
script function, refer to the following manual.
GT Designer3 Version1 Screen Design
Manual(Drawing)
27. STATUS OBSERVATION FUNCTION
30. SCRIPT FUNCTION
28.6 Device Range that Can Be Set
28
29
30
031AH
31
32
33
34
35
28 - 5

Advertisement

Table of Contents
loading

Table of Contents