36.4 GOT Side Settings

36.4.1 Setting communication
interface (Communication
settings)
Set the channel of the equipment connected to the GOT.
2.
1.
Select [Common]
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: KOYO
• Controller Type: KOYO KOSTAC/DL
• I/F: Interface to be used
• Driver: KOYO KOSTAC/DL
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.
36.4.2 Communication detail settings
Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
17.1.2 I/F communication setting
36 - 12
36. CONNECTION TO KOYO EI PLC
36.4 GOT Side Settings
Click!
[Controller Setting] from the
36.4.2 Communication detail settings
Make the settings according to the usage environment.
Item
Transmission
Speed
Data Bit
3.
Stop Bit
4.
Parity
Retry
Timeout Time
Delay Time
Host Address
POINT
POINT
POINT
(1) Communication interface setting by the Utility
The communication interface setting can be
changed on the Utility's [Communication setting]
after writing [Communication Settings] of project
data.
For details on the Utility, refer to the following.
12. COMMUNICATION INTERFACE SETTING
(COMMUNICATION SETTING)
(2) Precedence in communication settings
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
Description
Set this item when change the
transmission speed used for
communication with the connected
equipment.
(Default: 9600bps)
Set this item when change the data
length used for communication
with the connected equipment.
(Default: 8bit)
Specify the stop bit length for
communications.
(Default: 1bit)
Specify whether or not to perform a
parity check, and how it is
performed during communication.
(Default: Odd)
Set the number of retries to be
performed when a communication
error occurs.
(Default: 3times)
Set the time period for a
communication to time out.
(Default: 3sec)
Set this item to adjust the
transmission timing of the
communication request from the
GOT.
(Default: 0ms)
Specify the host address (station
No. of the GOT to which the PLC is
connected) in the connected
network.
(Default: 1)
Range
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
7bits/8bits
1bit/2bits
None
Even
Odd
0 to 5times
3 to 50sec
0 to 300ms
1 to 90